Why arc flash labels matter
A label translates engineering calculations into information an electrician can act on at the moment they open a cover. It tells them the voltage, how far the arc flash hazard extends, and what level of protection is needed. An inaccurate or outdated label can be worse than none, because it creates false confidence.
NEC field-marking requirements
The National Electrical Code (NFPA 70), Section 110.16, requires electrical equipment such as switchboards, switchgear, panelboards, industrial control panels, meter socket enclosures and motor control centers in other than dwelling units, that are likely to require examination, adjustment, servicing or maintenance while energized, to be field or factory marked to warn qualified persons of potential arc flash hazards. Recent NEC editions add requirements for certain service equipment to carry additional information such as the available fault current and the date of the calculation. The edition adopted in your jurisdiction determines the exact requirement.
NFPA 70E label content
NFPA 70E requires equipment labels to contain, at minimum:
- Nominal system voltage
- Arc flash boundary
- At least one of the following:
- Available incident energy and the corresponding working distance, or
- The arc flash PPE category (but not both incident energy and PPE category on the same label), or
- Minimum arc rating of clothing, or
- Site-specific level of PPE
Many studies also put shock approach boundaries (limited and restricted), the equipment ID, the date of the analysis and the study reference on the label. The method used to calculate the label data must be documented, and the owner of the equipment is responsible for documenting, installing and maintaining the labels.
Label durability and placement
Labels need to be legible and durable for the environment. Texas facilities face heat, UV exposure on outdoor equipment, humidity and salt air along the coast, and chemical exposure in process plants. Engineering firms typically specify label materials suitable for industrial use. Labels should be placed where they're clearly visible to a worker before they approach exposed energized parts — usually on the front of the equipment near the door or cover.
When labels must be updated
Labels must reflect the current arc flash risk assessment. NFPA 70E requires that assessment to be reviewed at least every five years and updated after major modifications or renovations. Typical triggers for relabeling include:
- A utility transformer change or service upgrade that changes available fault current
- Adding or replacing generators, UPS systems or transformers
- Breaker, fuse or relay replacements or settings changes
- New panels, MCCs or switchgear
- Reconfigured feeders or new operating modes
- Damaged, faded or missing labels
It is also important to remember that a change in one part of the system can affect equipment far downstream. That's why label updates should be driven by an updated study rather than by replacing individual labels in isolation.
Labels-only requests
If your facility has a recent, valid study and you simply need labels reprinted, replaced or installed, select “Labels only” in the form. The engineering firm will need to review the existing study to confirm it's current. If the study is older than five years or the system has changed, they'll likely recommend an update first. See our cost guide for indicative pricing, or the NFPA 70E guide for the bigger picture.
How the labeling process works
After the study's incident energy analysis is complete, the engineering firm generates labels for each assessed equipment location. Depending on the proposal, the firm may install them during a follow-up visit, or supply them for your electricians to install. Always confirm who is responsible for installation in the proposal.